Table 4
Sequence of turbine trip accident.
Time | Event |
---|---|
0 s | Turbine trip |
0.15 s | Steam line and feedwater line isolation |
3 s | Station blackout. Coolant pumps coast down with their inertia. Minimum DNBR is reached (3.87) |
4.6 s | Reactor scram actuated by pumps low speed |
6 s | Emergency condensers are connected to SGs |
7.3 s | Maximum primary pressure and temperature are reached (167 bar, 322 °C) |
14 s | Maximum secondary pressure and temperature are reached (83 bar, 298 °C) |
8 min | Heat removed by ECs becomes greater than heat removed by SGs which is greater than decay heat |
90 min | Low pressurizer level leads to CMTs injection and passive primary cooling actuation |
100 min | Primary temperature falls below 215 °C |
150 min | CMTs natural circulation stops |
167 min | End of simulation |