Open Access

Table 8

Comparative results from the hydraulic analyses. Model I.

Data obtained by using
Pipenet (L/s)
Data obtained by using
Flowmaster (L/s)
Flow through P1 118.4 115
Flow through P2 118.4 114
Flow through HX1 106.6 104
Flow through HX2 106.6 103
Flow through
inlet collectors
HD6: 106.6 HD6: 104
HD2: 0 HD2: 1.4 × 10–10
HD4: 0 HD4: 2.27 × 10–9
HD8: 106.6 HD8: 103
Flow through
outlet collectors
HD5: 106.6 HD5: 104
HD1: 0 HD1: 1.85 × 10–9
HD3: 0 HD3: 1.73 × 10–9
HD7: 106.6 HD7: 103
Flow through
PHTS pumps
P1: 0 P1: 4 × 10–10
P2: 0 P2: 1.55 × 10–9
P3: 58.6 P3: 54
P4: 58.6 P4: 54
Flow through
fuel channels
R1: 0 R1: 2.15 × 10–10
R2: 53 R2: 50
R3: 0 R3: 1.79 × 10–9
R4: 53 R4: 50

Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.

Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.

Initial download of the metrics may take a while.