Open Access

Table 9

Comparative results from the hydraulic analyses. Model II.

Data obtained by using
Pipenet (L/s)
Data obtained by using
Flowmaster (L/s)
Flow through P1 118.4 115
Flow through P2 0 1.7
Flow through HX1 106.6 104
Flow through HX2 0.3 1.9
Flow through
inlet collectors
HD6: 106.6 HD6: 104
HD2: 0 HD2: 7.75 × 10–12
HD4: 0 HD4: 7.3 × 10–12
HD8: 0.3 HD8: 1.9
Flow through
outlet collectors
HD5: 106.6 HD5: 104
HD1: 0 HD1: 4.14 × 10–12
HD3: 0 HD3: 4.11 × 10–11
HD7: 0.3 HD7: 1.9
Flow through
PHTS pumps
P1: 0 P1: 4.97 × 10–12
P2: 0 P2: 5.2 × 10–12
P3: 71 P3: 67
P4: 35.4 P4: 34.8
Flow through
fuel channels
R1: 0 R1: 6.9 × 10–12
R2: 38 R2: 36.7
R3: 0 R3: 5 × 10–12
R4: 37.9 R4: 36.7

Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.